Faran’s “Vigor RT” uses Online Double Conversion / High Frequency UPS technology and protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With 6000 VA capacity, this product is suitable for banks, medical centers, telecommunications, airports, IT centers, security systems, quality-control equipment and offices. Depending on battery capacity and charging time, it can provide backup power after an outage. Output voltage is selectable at 208/220/230/240 V; rated input is 208/220/230/240 V, input range is 110–300 V, output frequency is 50 or 60 Hz and input frequency range is 40–70 Hz. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 50 dB. Faran Vigor RT features a wide input range, Online High Frequency UPS technology, true sine-wave output with THD below 2% at linear load, advanced battery management (ABM), automatic charging with inverter off, EMI/RFI filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. The useful output power is 2700 W. This UPS has no internal battery and requires 16–20 external battery cells.
تماس بگیرید
149 in stock
| Capacity | 6kVA / 6kW | |
| INPUT | ||
| Input Wiring | Single-phase three-wire (1ɸ + N + PE) | |
| Rated Voltage | 208 / 220 / 230 / 240 Vac; | |
| Voltage Range | 110 ~ 176 Vac (Linear derating between 50% and 100% load); 176 ~ 288 Vac (no derating) | |
| Rated Frequency | 50 / 60 Hz (auto-sensing) | |
| Frequency | 40 ~ 70 Hz | |
| Power Factor | ≥0.99 | |
| Bypass Voltage Range | – 40% ~ + 15% (settable) | |
| Total harmonic distortion (THDi) | ≤ 5% | |
| OUTPUT | ||
| Output Wiring | Single-phase (L – N) | |
| Rated Voltage | 208 (PF=0.9) / 220 /230 / 240 VAC | |
| Voltage Regulation | ±1% | |
| Frequency | Synchronized to bypass in Mains Mode; 50 / 60 ±0.1% Hz in Battery Mode | |
| Waveform | sinusoidal | |
| Power Factor | 1 | |
| Total Harmonic Distortion (THDv) | ≤1%(Linear Load); ≤4%(Non-Linear Load) | |
| Crest Factor | 3:1 | |
| Overload Capability | 105%~110% for 10 min, 110%~125% for 1 min, 126%~150% for 30 s | |
| BATTERIES | ||
| DC Voltage | 192 Vdc (192 ~ 240 Vdc settable) | |
| Number of battery | 16 pcs (16 ~ 20 settable) | |
| Inbuilt Battery Standard Model | 12V / 9Ah * 16 | |
| Charge Current | Standard model: 1A; Long time model: 5A (default), 1~5A settable; 12A (optional) | |
| Recharge Time | Standard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery |
|
| SYSTEM | ||
| Efficiency | ≥94% at 100% load, max 94.5% at 60% load, ≥98% in ECO mode | |
| Transfer Time | 0 ms | |
| Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
|
| Max number of parallel connections | 4 | |
| Communications | RS232(standard), USB / RS485 / dry contacts / SNMP / Battery temperature compensation (optional) |
|
| Display | LCD + LED | |
| OTHERS | ||
| Operation temperature | 0°C ~ 40°C | |
| Storage temperature | -25°C ~ 55°C (without battery) | |
| Relative humidity | 0 ~ 95% (non-condensing) | |
| Altitude | ≤1000 m, derating 1% for each additional 100 m | |
| IP rating | IP 20 | |
| Noise Level at 1m | ≤ 55dB | |
| Dimensions (W × D × H)(MM) | 440 * 660 * 176 (S) 440 * 580 * 88 (H) |
|
| Packaged Dimensions (W × D × H)(MM) | 554 * 792 * 418 (S) 514 * 696 * 168 (H) |
|
| Net Weight(kg) | 58 (S), 12 (H) | |
| Gross Weight(kg) | 68 (s), 14 (H) | |
Reviews