Faran’s “Titan Plus” uses Double Conversion (Online High Frequency UPS) technology and protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 10 kVA, this product is suitable for banks, medical centers, IT centers, security systems, telecommunications, quality-control equipment and offices. Depending on battery capacity and charging time, it can supply backup power after a mains outage. Output voltage is selectable at 220/230/240 V; rated input is 380/400/415 V and the input-voltage range is 305–499 V. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 58 dB. Faran Titan Plus features a wide input range, Online Double Conversion, true sine-wave output with THD below 1% at linear load, advanced battery management (ABM), automatic charging with inverter off, EMI/RFI filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. The UPS has no internal battery and requires 16–20 external battery cells.
تماس بگیرید
149 in stock
| Capacity | 10kVA / 10kW | ||
| INPUT | |||
| Input Wiring | Three-phase five-wire (3ɸ + N + PE) | ||
| Rated Voltage | 380 V / 400 V/ 415 Vac | ||
| Voltage Range | 190 ~ 305 Vac (Linear derating between 50% and 100% load); 305 ~ 499 Vac (no derating) |
||
| Rated Frequency | 50 / 60 Hz (auto-sensing) | ||
| Frequency | 40-70 Hz | ||
| Power Factor | ≥0.99 | ||
| Bypass Voltage Range | – 40% ~ + 15% (settable) | ||
| Total harmonic distortion (THDi) | ≤ 5% | ||
| OUTPUT | |||
| Output Wiring | Single-phase three-wire (1ɸ + N + PE) | ||
| Rated Voltage | 208 (PF=0.9) / 220 /230 / 240 VAC | ||
| Voltage Regulation | ±1% | ||
| Frequency | Synchronized to bypass in Mains Mode; 50 / 60 ±0.1% Hz in Battery Mode | ||
| Waveform | sinusoidal | ||
| Power Factor | 1 | ||
| Total Harmonic Distortion (THDv) | ≤1%(Linear Load); ≤3%(Non-Linear Load) | ||
| Crest Factor | 3:1 | ||
| Overload Capability | 102%~110% for 10 min, 110%~125% for 1 min, 125%~150% for 30 s | ||
| BATTERIES | |||
| DC Voltage | 192 Vdc (192 ~ 240 Vdc settable) | ||
| Number of battery | 16 pcs (16 ~ 20 settable) | ||
| Inbuilt Battery Standard Model | 12V / 9Ah * 16 | ||
| Charge Current | Standard model: 1A; Long time model: 5A (default), 1~5A settable; 10A (optional) | ||
| Recharge Time | Standard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery |
||
| SYSTEM | |||
| Efficiency | ≥94% at 100% load, max 95% at 60% load, ≥98% in ECO mode | ||
| Transfer Time | 0 ms | ||
| Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
||
| Max number of parallel connections | 4 | ||
| Communications | RS232(standard), USB / RS485 / dry contacts / SNMP / batterytemperature compensation (optional) |
||
| Display | LCD + LED | ||
| OTHERS | |||
| Operation temperature | 0°C ~ 40°C | ||
| Storage temperature | -25°C ~ 55°C (without battery) | ||
| Relative humidity | 0 ~ 95% (non-condensing) | ||
| Altitude | ≤1000 m, derating 1% for each additional 100 m | ||
| IP rating | IP 20 | ||
| Noise Level at 1 m | ≤ 58dB | ||
| Dimensions (W × D × H)(MM) | 191 * 495 * 711 (S) 191 * 495 * 350 (H) |
||
| Packaged Dimensions (W × D × H)(MM) | 310 * 685 * 941 (S) 318 * 617 * 475 (H) |
||
| Net Weight(kg) | 64 (s) 18.5 (H) | ||
| Gross Weight(kg) | 72 (s) 20 (H) | ||
Reviews