Titan Plus

Online High frequency UPS

6kva

 

Faran’s “Titan Plus” uses Online Double Conversion / High Frequency UPS technology and protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 6000 VA, this product is suitable for banks, medical centers, IT centers, security systems, quality-control equipment and offices. Depending on battery capacity and charging time, it can supply backup power after an outage. Output voltage is selectable at 208/220/230/240 V; rated input is 208/220/230/240 V, input range is 110–300 V, output frequency is 50 or 60 Hz and input frequency range is 40–70 Hz. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 50 dB. Faran Titan Plus features a wide input range, Online Double Conversion, true sine-wave output with THD below 2% at linear load, advanced battery management (ABM), automatic charging with inverter off, EMI/RFI filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. The UPS includes batteries and requires twenty 9 Ah battery cells for operation.

Download catalog

تماس بگیرید

149 in stock

توضیحات محصول
6kVA / 5.4kW Capacity
INPUT
208V/220V/230V/240VAC Rated Voltage
Half load(110-300)±5VAC; Full load(160-300)±5VAC Voltage Range
40-70Hz(Auto sensing) Frequency
≥99% Power Factor
160V~Rated Output Voltage+32V Bypass Voltage Range
OUTPUT
208V/220V/230V/240VAC Setting available via LCD Voltage
±1% Voltage Regulation
45-55Hz or 55-65Hz(Synchronized range); 50/60±0.2Hz(Battery mode) Frequency
Pure sine wave Waveform
3:1 Crest Factor
≤2%(Linear load); ≤5%(Non-linear load) Harmonic Distortion
AC mode to battery mode: 0ms
Inverter model to bypass mode: 0ms
Transfer Time
105%-125%:Transfer to bypass after 3 mins;
125%-150%:Transfer to bypass after 30s;
>150%Transfer to bypass after 100 ms
Overload Capability
EFFICIENCY
≥92% AC Mode
≥91% Battery Mode
≥98% ECO Mode
BATTERY
240V DC Voltage
20×9Ah Inbuilt Battery of Standard Model
1A Standard Model Charge Current
1A/3A/5A/8A Long Time Model
8 hours recover to 90% capacity Typical Recharge Time
ALARM
Beep/4s Utility Failure
Beep/1s Battery Low
Beep Twice/1s Overload
Long Beep UPS Fault
ENVIRONMENT
20~90%RH@0~40%°C(non-condensing) Humidity
≤55dB(1m) Noise Level
MANAGEMENT
Supports Windows®98/2000/2003/XP/Vista/2008/Windows®7/8 Standard RS-232, Optional USB
Power management from SNMP manager and web browser Optional SNMP
PHYSICAL
262×514×455(H),262×514×735(S) Dimension (mm)WXDXH
365×605×610(H),390×625×937(S) Packaging Dimension(mm)WXDXH
22.1(H),81.5(S) Net Weight(kg)
25.2(H),89.5(S) Gross Weight(kg)