Faran’s “Galaxy S” uses Double Conversion (Online High Frequency UPS) technology with a transformer-based design, protecting equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 80 kVA, this product is suitable for banks, medical equipment (MRI, CT scan), IT centers, nonlinear industrial loads, offices and quality-control equipment. Depending on battery capacity and charging time, it can supply the load after a power outage (backup). Output voltage is selectable at 380/400/415 V; rated input is 380/400/415 V and the input-voltage range is ±25% of nominal. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 65 dB. Faran Galaxy features a wide input-voltage range, Online Double Conversion, true sine-wave output, advanced battery management (ABM), automatic charging with the inverter off, a thyristor rectifier, EMI/RFI input/output filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. The UPS has no internal battery and requires 28–32 external battery cells.

Download catalog

تماس بگیرید

149 in stock

توضیحات محصول
Capacity 100 kVA
INPUT
Rated Voltage 380 V / 400 V / 415 Vac
Voltage range ± 25 %
Rated frequency 50 / 60 Hz
Frequency range 50 / 60 Hz  ± 5 Hz
Power factor ≥0.95 (with filter)
Bypass voltage range ± 20 % (settable)
Delayed start of rectifier 1 ~ 300 s (settable via display panel)
ECO voltage range ± 10 % (settable)
OUTPUT
Voltage 380 V / 400 V / 415 Vac
Voltage regulation ± 1 %
Frequency Synchronized with utility in main mode ; 50/60Hz ±0.1% in battery mode
Waveform Synusoidal
Power factor 0/9
Crest factor 3:1
Transfer time AC mode to battery mode : 0ms
Inverter mode to bypass mode : 0ms
Inverter mode to ECO mode : 0 ~ 4ms
Overload 105% :long time running
110% ~ 125% for 10min
125% ~ 200% for 200ms
>200% for 100ms
Slight adjustment of inverter output voltage ±5V
BATTERIES
DC voltage 12V * configured battery number (settable via display panel)
Number of battery 28 ~ 32 pcs (settable)
Charging current 10A default /settable
Charging Three-stage charging, auto switch floating / equalizing charge
Battery state display Display battery backup time , battery remaining capacity
Battery selt-test Settable periodic self-test; manually configurable test time and voltage
SYSTEM
Efficiency In line mode: Max 93% ; ECO mode: ≥98%
Max. Parallel numbers 6
Protections Short-circuit-overload-overvoltage-undervoltage-low battery-overtemperature-fan fault
Communication RS232/RS485/dry contacts (standard) , SNMP (optional)
IP rating IP20
EMI EN62040-2
EMS IEC61000-4-2 (ESD)
IEC61000-4-3 (RS)
IEC61000-4-4 (EFT)
IEC61000-4-5 (surge)
OTHERS
Humidity 0~95% RH@0~40˚C(non-condensing)
Noise level 65 dB
Dimensions (W * D *H) (mm) 700*800*1700
Packaged dimensions (W * D * H) (mm) 800*900*1850
Net / Gross weight (kg) 630/660

 