پشتیبانی آنلاین

0698 767 0933

Galaxy 250 kVA UPS

Galaxy

Online high frequency UPS

250KVA  (3:3)

Faran’s “Galaxy” uses Double Conversion (Online High Frequency UPS) technology with a transformer-based structure. It protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 250 kVA, this product is suitable for banks, medical equipment (MRI, CT scan), IT centers, nonlinear industrial loads and offices. Depending on battery capacity and charging time, it can supply the load after a power outage (backup). Output voltage is selectable at 380/400/415 V; rated input is 380/400/415 V and the input-voltage range is 346–456 V. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 65 dB. Faran Galaxy features a wide input range, Online Double Conversion, true sine-wave output with THD below 2% at linear load, FULL IGBT design, advanced battery management (ABM), automatic charging with inverter off, EMI/RFI filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor and ECO Mode. The UPS has no internal battery and requires 48–52 external battery cells.

Download catalog

تماس بگیرید

149 in stock

توضیحات محصول
CAPACITY 250kVA /
225 kw
INPUT
Input wiring Three-phase five-wire (3 + N + PE)
Rated voltage 380V / 400V / 415Vac
Voltage range 346 V ~ 456 V (full load), 304 V ~ 346 V (power derating  10%)
Rated frequency 50 / 60 Hz
Frequency range 50 / 60 Hz ± 5 Hz
Power factor ≥ 0.99
Total harmonic distortion (THDI) ≤ 3%
Input current limiting 1.1 times of rated current ( 0.1 ~ 1.1 settable )
Rectifier delay start 10 s ( 1 ~ 300 settable )
Bypass voltage range ± 20% ( settable)
OUTPUT
output wirig Three-phase five-wire (3Ф + N + PE)
Rated voltage 380 V / 400 V / 415 Vac
Voltage regulation accuracy ± 1%
Voltage regulation 0 V ( ± 1 ~ 5 V settable)
Frequency synchronized with utility in mains mode ; 50 / 60 Hz ± 0.1% in battery mode
Power factor 0/9
Total harmonic distortion (THDV) ≤ 2% ( linear load);  ≤ 5% ( non – linear load)
Crest factor 3:1
Overload capability 105% ~ 110% for 60 min , 110% ~ 125% for 10 min
BATTERY
DC voltage 600 Vdc ( support 576 Vdc / 588 Vdc / 612 Vdc / 624 Vdc )
Number of batteries 50 pcs 12 V ( support 48 / 49 / 51 / 52 pcs )
Charging current Charging rate ( settable) × battery capacity ( settable) × number of battery groups ( settable)
SYSTEM
Efficiency Line mode ≥ 94%
ECO mode ≥ 98%
Max.number of parallel connections 6
Protections Short-circuit.Overload. Overtemperature. Overvoltage.Undervoltage. Battery low voltage and fan failure
Communications Standard configuration: RS232, RS485, dry contacts
Optional configuration: SNMP card, temperature compensation, SMS alarms
Display 5.7 inches LCD touch screen
OTHERS
Operating temperature 0 ~ 40°C
Storage  temperature -25°C ~ 55°C ( without battery )
Humidity 0 % ~ 95% (non-condensing)
Altitude ≤ 1000 m , Above 1000 m , derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1 m < 65 dB
Dimensions ( W x D x H ) (mm) 1210 × 860 × 1950
Packaged dimensions ( W x D x H ) ( mm) 1300 × 1000 × 2200
Net / Gross weight  (kg) 1135/1200

 

Reviews

There are no reviews yet.

Be the first to review “Galaxy 250 kVA UPS”

Your email address will not be published. Required fields are marked *

محصول فعلی به سبد خرید اضافه شد