پشتیبانی آنلاین

0698 767 0933

Comet Plus UPS 10 kVA

Comet plus

Online high frequency UPS

10KVA (3:3)

Faran’s “Comet Plus” uses Double Conversion (Online High Frequency UPS) technology and protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 10 kVA, this product is suitable for banks, medical centers, IT centers, security systems, telecommunications, offices and quality-control equipment. Depending on battery capacity and charging time, it can provide backup power after a mains outage. Output voltage is selectable at 380/400/415 V; rated input is 380/400/415 V and the input-voltage range is 304–478 V. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 55 dB. Faran Comet Plus features a wide input range, Online Double Conversion, true sine-wave output with THD below 1% at linear load, advanced battery management (ABM), automatic charging with inverter off, EMI/RFI filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. The UPS has no internal battery and requires 30–40 external battery cells.

Download catalog

تماس بگیرید

149 in stock

توضیحات محصول
CAPACITY 10kVA / 10kW
INPUT
Rated voltage  380 V / 400 V / 415 Vac (L-L)
Voltage range 304 ~ 478 Vac (L-L) , Full load
228 ~ 304 Vac(L-L),load decrease linearly according to the min phase voltage
Rated frequency 50 / 60 Hz (auto-sensing)
Frequency range 40 ~ 70 Hz
Power factor ≥0.99
Total harmonic distortion (THDI) ≤3% (full linear load)
Bypass voltage range Selectable , default -20% ~ +15%
Up limited: +10%, +15%, +20% ; Down limited: -10%, -15%, -20%, -30%, -40%
Bypass frequency range selectable , ± 1Hz , ± 3Hz, ± 5Hz
Bypass overload 125%: Long term operation; 125% ~ 130% : 10 min; 130% ~ 150%: 1min; 150% ~ 400%: 1s; >400 less than 200ms
OUTPUT
Rated Voltage  380 V / 400 V / 415 Vac(L-L)
Voltage regulation ± 1% (full linear load)
Frequency Synchronized with utility in mains mode; 50/60 ± 0.1% in battery mode
Waveform Sinusoidal
Power factor 1
Crest factor 3:1
Total harmonic distortion (THDV) ≤ 1% (full linear load) ≤ 3% (full non-liner load according to IEC/EN62040-3)
Overload <110%, 60min; 110% ~ 125%, 10min; 125% ~ 150%, 1min; >150%, 200 ms
BATTERY
DC voltage ±240VDC (Selectable, 30 ~ 40 pcs)
Inbuilt battery (standard model) (10+10)*9AH
Charging current 10A Max
Charging Voltage precision 1%
Typical recharge time Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery
SYSTEM
Efficiency 95% Max
Transfer time 0 ms
Max,number of parallel connections 4
Protections Short-circuit, overload, overtemperature,
battery low voltage, over voltage, undervoltage and fan fault
Communications RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard)
SNMP card, Wi-Fi card, GPRS card, SMS alarms (Optional)
Display LED + 5 inches LCD touch screen
OTHERS
Operating temperature 0˚C  ~  40˚C
Storage temperature -40˚C  ~  70˚C
Relative humidity 0 ~ 95% (Non-condensing)
Altitude <1000m, Load derated 1% per 100m from 1000 ~ 2000m
IP rating IP 20
Noise level at 1 m 55dB@100% load,
52dB @ 50% load
Dimensions (W × D × H)(mm) 250*720*560 (S)
250*720*560 (H)
Packaged dimensions(W × D × H)(mm) 350*800*722(S)
350*800*718 (H)
Net weight (kg) 82 (S)  31 (H)
Gross weight(kg) 93 (S)  40 (H)