پشتیبانی آنلاین

0698 767 0933

Gri Power 200 kVA UPS

Galaxy-S

Online UPS

120KVA (3:3)

 

Faran’s “Galaxy S” uses Double Conversion (Online High Frequency UPS) technology with a transformer-based design, protecting equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 10 kVA, this product is suitable for banks, medical equipment (MRI, CT scan), IT centers, nonlinear industrial loads, offices and quality-control equipment. Depending on battery capacity and charging time, it can supply the load after a power outage (backup). Output voltage is selectable at 380/400/415 V; rated input is 380/400/415 V and the input-voltage range is ±25% of nominal. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 65 dB. Faran Galaxy features a wide input-voltage range, Online Double Conversion, true sine-wave output, advanced battery management (ABM), automatic charging with the inverter off, a thyristor rectifier, EMI/RFI input/output filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and ECO Mode. . The UPS has no internal battery and requires 28–32 external battery cells.

Download catalog

تماس بگیرید

149 in stock

توضیحات محصول
Rated capacity 200 kVA/200 kW
Number of power modules 4
Rated capacity of power module 50 kVA
INPUT
Input wiring 3 PH + N + PE
Rated voltage 380 / 400 / 415 Vac
Voltage range 138 ~ 485 Vac (305 ~ 485 Vac without power downgrading;
138 ~ 305 Vac with linear downgrading 40%)
Input frequency 40 ~ 70 Hz
Power factor ≥ 0.99
Current distortion ˂ 3%
BATTERIES
Battery voltage ±240 Vdc (±180 ,±192 ,±204 , ±216 , ±228 , ±252 , ±264 , ±276 selectable)
Number of battery 40 pcs 12 V batteries (30/32/34/36/38/42/44/46 pcs selectable)
OUTPUT
Output wiring 3 PH + N + PE
Rated voltage 380 / 400 / 415 / Vac ±1%
Frequency Synchronized with utility in mains power mode ;
50 Hz / 60 Hz ± 0.25% in battery mode
Power factor 1
Voltage distortion ≤ 1% with linear load  / ≤ 3% with non-linear load
Crest factor 3:1
Inverter overload capacity 105 % < load ≤ 110% : transfer to bypass in 60 min
110 % < load ≤ 125% : transfer to bypass in 10 min
125 % < load ≤ 150% : transfer to bypass in 1 min
load > 150% : transfer to bypass in 200 ms
Bypass overload capacity Load ≤ 135% for long term ; < 1000 % load for 100 ms
SYSTEM
Efficiency 96/50%
Max. number of parallel connection 4 Units
Transfer time 0 ms
Protections Short circuit protection , overload protection , over temperature protection , battery low
voltage protection , output over/low voltage protection , fans failure protection etc
Communications RS485 , dry contacts , SNMP
Display 7 inches LCD touch screen
OTHERS
Operation temperature 0 ~ 40˚C
Storage temperature -40˚C ~ +70˚C
Humidity 0 ~ 95% (non-condensing)
Altitude ≤1000 m. Above, derating 1% for each additional 100m
Protection level IP20
Noise level at 1m < 65 dB
Cabinet demensions (W*D*H){mm) 600 * 850 * 2000
UPS module demensions (W*D*H){mm) 440 * 620 * 130
Cabinet weight (kg) 233
Power module weight (kg) 32