پشتیبانی آنلاین

0698 767 0933

Gri Power 600 kVA UPS

Gri Power

600KVA

PF  1.0

 

Faran’s “GriPower” uses Double Conversion (Online High Frequency UPS) technology in a modular architecture, with each module rated at 50 kVA. It protects equipment against mains fluctuations, sudden voltage changes, common-mode noise, phase faults, lightning and similar disturbances. With a capacity of 600 kVA, this product is suitable for banks, IT centers, security systems, telecommunications, quality-control equipment and offices. Depending on battery capacity and charging time, it can power the load after a mains outage (backup). Output voltage is selectable at 415/400/380 V; rated input is 415/400/380 V and the input-voltage range is 305–485 V. The front-panel display shows battery capacity, load, input/output voltage and frequency, and other operating values. The time required to fully charge the batteries depends on battery capacity. Operating temperature is 0–40°C and operating noise is below 58 dB. Faran GriPower features a wide input range, Online Double Conversion, true sine-wave output with THD below 1% at linear load, advanced battery management (ABM), automatic charging with the inverter off, EMI/RFI input/output filters, advanced PFC and network-based UPS monitoring. The unit also includes a DSP processor with Cold Start and Soft Start capabilities. The UPS has no internal battery and requires 30–46 optional external battery cells.

Download catalog

تماس بگیرید

توضیحات محصول
Rated capacity 600 600kVA/ kW
Number of power modules 12
Rated capacity of power module 50 kVA
INPUT
Input wiring 3 PH + N + PE
Rated voltage 380 / 400 / 415 Vac
Voltage range 138 ~ 485 Vac (305 ~ 485 Vac without power downgrading;
138 ~ 305 Vac with linear downgrading 40%)
Input frequency 40 ~ 70 Hz
Power factor ≥ 0.99
Current distortion ˂ 3%
BATTERIES
Battery voltage ±240 Vdc (±180 ,±192 ,±204 , ±216 , ±228 , ±252 , ±264 , ±276 selectable)
Number of battery 40 pcs 12 V batteries (30/32/34/36/38/42/44/46 pcs selectable)
OUTPUT
Output wiring 3 PH + N + PE
Rated voltage 380 / 400 / 415 / Vac ±1%
Frequency Synchronized with utility in mains power mode ;
50 Hz / 60 Hz ± 0.25% in battery mode
Power factor 1
Voltage distortion ≤ 1% with linear load  / ≤ 3% with non-linear load
Crest factor 3:1
Inverter overload capacity 105 % < load ≤ 110% : transfer to bypass in 60 min
110 % < load ≤ 125% : transfer to bypass in 10 min
125 % < load ≤ 150% : transfer to bypass in 1 min
load > 150% : transfer to bypass in 200 ms
Bypass overload capacity Load ≤ 135% for long term ; < 1000 % load for 100 ms
SYSTEM
Efficiency 96/50%
Max. number of parallel connection 4 Units
Transfer time 0 ms
Protections Short circuit protection , overload protection , over temperature protection , battery low
voltage protection , output over/low voltage protection , fans failure protection etc
Communications RS485 , dry contacts , SNMP
Display 7 inches LCD touch screen
OTHERS
Operation temperature 0 ~ 40˚C
Storage temperature -40˚C ~ +70˚C
Humidity 0 ~ 95% (non-condensing)
Altitude ≤1000 m. Above, derating 1% for each additional 100m
Protection level IP20
Noise level at 1m < 68 dB
Cabinet demensions (W*D*H){mm) 1400 * 850 * 2000
UPS module demensions (W*D*H){mm) 440 * 620 * 130
Cabinet weight (kg) 617
Power module weight (kg) 32

Reviews

There are no reviews yet.

Be the first to review “Gri Power 600 kVA UPS”

Your email address will not be published. Required fields are marked *

محصول فعلی به سبد خرید اضافه شد